Abstract
Filmwise condensation heat-transfer measurements were performed on horizontal smooth and roped titanium tubes using steam. The roped tubes were a commercially available tube (KORODENSE) with a normal pitch of 7 mm. To further enhance the outside heat-transfer coefficient of both the smooth and roped tubes a wire was tightly wrapped around the tubes. To see the effect that the wire diameter and wire pitch had on the enhancement, 3 difference wire diameters were used (nominal diameters of 0.5, 1.0, 1.6 mm) giving a range of wire pitch to wire diameter ratio of between 2 and 9. Tests were conducted under vacuum and atmospheric pressure condition. The data reduction technique used to modified Wilson plot. Results obtained for the wire-wrapped smooth titanium tubes showed a maximum enhancement of 30% as compared to a smooth titanium tube. This was for a tube using a 0.5 mm wire diameter (P/D(w) = 7.92), corresponding to a fraction of the tube covered by the wire of 12%. The LPD KORODENSE titanium tube showed an enhancement of 20% as compared to a smooth titanium tube for both atmospheric and vacuum pressures. The addition of wrapping a wire in the grooves of the LPD tube showed no further significant enhancement for the three wire diameters tested.
Type
Thesis
Description
Series/Report No
Department
Mechanical Engineering
Organization
Naval Postgraduate School (U.S.)
Identifiers
NPS Report Number
Sponsors
Funder
Format
229 p.
Citation
Distribution Statement
Approved for public release; distribution is unlimited.
Rights
This publication is a work of the U.S. Government as defined in Title 17, United States Code, Section 101. Copyright protection is not available for this work in the United States.