The effect of condensate inundation on steam condensation heat transfer in a tube bundle

Download
Author
Brower, Steven K.
Date
1985-06Advisor
Marto, P.J.
Wanniarachchi, A.S.
Metadata
Show full item recordAbstract
Steam-condensation heat-transfer measurements were made
using a 5-tube in-line test condenser with an additional
perforated tube to simulate up to 30 active tubes. Results
were obtained for smooth tubes, wire-wrapped tubes and
dropwise-coated tubes. The average outside heat-transfer
coefficient for 30 smooth tubes was 0.64 times the Nusselt
coefficient for the first tube. A total of eight wirediameter
and wire-pitch combinations were tested: 1.6-mmdiameter
wire wrapped at 16 mm, 7.6 mm and 4 mm wire pitches,
1 . 0-mm-diameter wire wrapped at 8 mm, 4 mm and 2 mm wire
pitches, and . 5-mm-diameter wire wrapped at 4 mm and 2 mm
wire pitches. The best bundle performance was obtained when
the tubes were wrapped with 1 .0-mm-diameter wire at a wire
pitch of 4 mm. This combination resulted in an average outside
heat-transfer coefficient for 30 tubes that was 1.15
times the value computed for the first tube using the Nusselt
theory. The average outside heat-transfer coefficient for
the 30 dropwise-coated tubes was 1.1 times the value of the
heat- transfer coefficient for the first tube in the tube
bundle. Utilizing either wire-wrapped tubes or dropwisecoated
tubes, it is possible to significantly reduce the
condenser surface area and overall size.
Collections
Related items
Showing items related by title, author, creator and subject.
-
The effect of condensate inundation on steam condensation heat transfer to wire-wrapped tubing
Kanakis, Georgios Dimitriou (Monterey, California. Naval Postgraduate School, 1983-06);Steam condensation heat transfer measurements were made in a 5-tube test condenser having an additional perforated tube to simulate up to 30 active tubes. Results were obtained for smooth tubes and roped tubes wrapped ... -
Filmwise condensation of steam on horizontal wire-wrapped smooth and roped titanium tubes
O'Keefe, Thomas Joseph (Monterey, California. Naval Postgraduate School, 1992-09);Filmwise condensation heat-transfer measurements were performed on horizontal smooth and roped titanium tubes using steam. The roped tubes were a commercially available tube (KORODENSE) with a normal pitch of 7 mm. To ... -
Pressure drop and heat transfer in a vertical internally heated annulus.
Liu, Kuang-Ming (Monterey, California: U.S. Naval Postgraduate School, 1961);The heat transfer and pressure drop of water flowing both upward and downward In an annulus were investigated. The data were obtained from a vertical narrow space annulus which was formed between 1.240 in. I. D. and ...