Nucleate pool boiling performance of smooth and finned tube bundles in R-113 and R-114/oil mixtures

Download
Author
Anderson, Carl Lee
Date
1989-06Advisor
Marto, Paul J.
Michael, Alexis G.
Second Reader
Joshi, Yogendra
Metadata
Show full item recordAbstract
Heat-transfer measurements were made for boiling of
refrigerants and refrigerant/oil mixtures from smooth and
finned tube bundles. The bundles contained 15 heated tubes
arranged in an equilateral triangular pitch of 19.1 mm. The
outside diameter of the smooth tubes (15.8 mm) was equal to
the diameter to the tip of the fins of the finned tubes.
The smooth tube bundle was tested in pure R-113 with varying
surface "histories" as well as with pure R-114 and R-ll4/oil
mixtures. The finned tube bundle was tested in pure R-114
and R-114/oil mixtures. Oil concentrations used were 1, 2,
3, 6, and 10% by mass.
Collections
Related items
Showing items related by title, author, creator and subject.
-
Nucleate pool boiling performance of finned and high flux tube bundles in R-114/oil mixtures
Akcasayar, Nezih (Monterey, California. Naval Postgraduate School, 1989-12);The heat transfer characteristics of pure R-114 and R-114/oil mixtures during nucleate pool boiling from a small bundle of finned and High Flux tubes were measured. The bundles had 5 instrumented and 10 additional heated ... -
Nucleate pool boiling performance of small High Flux and Turbo-B tube bundles in R-114 oil mixtures
Eraydin, Hakan (Monterey, California: Naval Postgraduate School, 1990-12);The U.S. Navy is constantly looking toward using more lightweight and compact heat exchangers. One of the areas of interest is the use of enhanced boiler tubes in the evaporator of a refrigerator plant, thereby cutting ... -
Condensation of refrigerants on small tube bundles
Mabrey, Burlin Davis (Monterey, California. Naval Postgraduate School, 1988-12);The construction of an apparatus for the condensation performance testing of a horizontal bundle of four tubes with various refrigerants was completed. The apparatus was instrumented, and data reduction software was developed ...